Undervoltage
Yaskawa · P1000
Was bedeutet Uv1 ?
The drive detected an undervoltage condition in the main circuit power supply. This indicates that the incoming AC voltage is below the acceptable operating threshold.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Measure the incoming AC line voltage (L1, L2, L3) at the drive's input terminals (R/L1, S/L2, T/L3) and compare it against the drive's nominal voltage rating and acceptable operating range.
- 2
Inspect all power wiring connections from the main disconnect/circuit breaker to the drive's input terminals for tightness and integrity.
- 3
Verify the main power supply circuit breaker or fuses feeding the drive for proper rating and operational status (e.g., trip status, continuity).
- 4
Check for voltage sags or brownouts on the incoming power supply, especially under load conditions, using a multimeter with min/max function or a power quality analyzer if available.