Pullout Detection
Yaskawa · P1000
Was bedeutet Sto ?
The drive has detected that the motor has pulled out of synchronization, often due to severe overload or insufficient torque. This results in the motor losing speed control.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Inspect mechanical load for binding, misalignment, or severe overload conditions that could cause motor pullout.
- 2
Verify drive parameters including motor nameplate data (voltage, current, frequency, RPM), acceleration/deceleration times, and current limit settings (e.g., C1-01) against motor specifications and application requirements.
- 3
Inspect motor power cabling for loose connections, damage, or signs of overheating at both the drive and motor terminals.
- 4
Measure motor phase currents while the drive attempts to run, checking for balance and excessive draw, which may indicate an overload or motor issue.