Drive Overload
Yaskawa · P1000
Was bedeutet oL2 ?
The drive itself has been operating under an overload condition, exceeding its continuous current rating. This can lead to drive shutdown or damage if not addressed.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Verify the mechanical load on the motor for any binding, obstruction, or excessive resistance that could lead to increased current draw.
- 2
Check drive parameters P2-01 (Motor Rated Current) and P6-01 (Overload Selection) against the motor nameplate data and application requirements.
- 3
Inspect motor power cables (U, V, W) for proper termination, insulation integrity, and signs of damage or short circuits between phases or to ground.
- 4
Monitor the drive's output current display and, if safely possible, independently measure motor phase currents to verify actual load against the motor's Full Load Amps (FLA).