oH

Heatsink Overheat

Yaskawa · P1000

Was bedeutet oH ?

The temperature of the drive's heatsink has exceeded its safe operating limit. This indicates insufficient cooling for the drive's power components.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Inspect the drive's heatsink fins and cooling fan for dust, debris, or obstructions.

  2. 2

    Verify the cooling fan's functionality and free rotation when the drive is powered on.

  3. 3

    Measure the ambient temperature within the drive's enclosure and verify it is within the specified operating range.

  4. 4

    Monitor the drive's output current (U1-01) on the display and compare it against the motor and drive rated currents for potential overload.

  5. 5

    Verify drive parameters such as carrier frequency (C1-01) and motor full load current (E1-04) against application requirements.