Too Many Speed Search Restarts
Yaskawa · J1000
Was bedeutet SEr ?
The drive has attempted Speed Search more times than the limit set in parameter b3-19. This typically indicates that the Speed Search parameters are incorrectly configured or that the motor is coasting in the opposite direction of the commanded run.
Häufige Ursachen
- Speed search acceleration time (b3-04) set too short for the load inertia, preventing successful synchronization.
- Speed search starting frequency (b3-05) configured too high or low relative to the actual coasting motor speed.
- Motor being actively driven by another device or exhibiting unexpected behavior during speed search attempts.
- Number of allowed speed search restart attempts (b3-19) set too low for application variability.
- Excessive mechanical friction or external forces preventing the motor from freely coasting.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
1. Increase the speed search restart limit parameter (b3-19) to a higher value (e.g., 5 or 10) to allow more attempts.
- 2
2. Extend the speed search acceleration time parameter (b3-04) to provide more duration for the drive to synchronize with motor speed.
- 3
3. Adjust the speed search starting frequency (b3-05) closer to the expected initial motor speed.
- 4
4. Confirm the motor is truly coasting and not being actively driven or braked by an external mechanism during speed search.
- 5
5. Check for excessive mechanical friction or load resistance that could prevent the drive from successfully identifying the motor's speed.
- 6
6. Monitor motor current and speed feedback during speed search attempts using drive diagnostics to identify synchronization issues.