Er - 02

Auto-Tuning Alarm

Yaskawa · F7 Drive

Was bedeutet Er - 02 ?

An alarm has been detected during the Auto-Tuning process, signaling a potential issue with the tuning setup or the motor/load configuration. While not a critical fault that stops the Drive, it warns of an incomplete or inaccurate auto-tuning result, which could lead to suboptimal motor performance or control issues.

Häufige Ursachen

  • Incorrect motor nameplate data (e.g., P2-01 to P2-06) entered into the Drive parameters.
  • Disconnected motor output phases (U, V, W) or high resistance connection preventing proper current flow.
  • Motor shaft physically jammed or encountering excessive mechanical resistance during the tuning sequence.
  • Auto-Tuning mode (A1-03) selected does not match the motor type or application requirements.
  • Drive output stage fault preventing proper current delivery during tuning.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Verify all motor nameplate parameters (P2-01: Motor Rated Power, P2-02: Motor Rated Current, P2-03: Motor Poles, P2-04: Motor Rated Speed, P2-05: Motor Rated Voltage, P2-06: Motor Rated Frequency) are correctly entered into the Drive.

  2. 2

    2. Power down the Drive, then use a multimeter to measure resistance between Drive output terminals U, V, W and between each terminal and ground to check for open circuits or shorts.

  3. 3

    3. Manually rotate the motor shaft to confirm it moves freely without binding or excessive friction.

  4. 4

    4. Set parameter A1-03 (Auto-Tuning Mode) to '1' (Static Tuning) if rotational tuning is not possible, or ensure '2' (Rotational Tuning) is appropriate for the application.

  5. 5

    5. Confirm the motor is completely decoupled from the load if rotational tuning is attempted, or that the load is appropriate for the selected tuning mode.

Alle Codes in diesem Handbuch durchsuchen (63)