Übersetzen...
PUF

DC Bus Fuse Open

Yaskawa · E7 Drive

Was bedeutet PUF ?

The Drive detects that the DC bus fuse has opened. This is typically caused by shorted output transistor(s) or output terminals, indicating a severe internal fault in the power circuit. The fuse opens to protect upstream components but requires addressing the underlying short.

Häufige Ursachen

  • Short circuit in one or more IGBTs (Insulated Gate Bipolar Transistors) in the drive's output power stage, causing excessive current and blowing the DC bus fuse.
  • Short circuit on the drive's output terminals (U/T1, V/T2, W/T3) to ground or between phases, usually due to motor cable insulation breakdown or motor winding fault.
  • Severe overcurrent condition caused by an extreme mechanical overload on the motor, leading to instantaneous current draw that exceeds the fuse rating.
  • Internal DC bus capacitor failure or short, though less common than IGBT failure, which can create a direct path for high current.
  • Incorrect fuse rating installed, or fuse degradation causing it to open prematurely under normal operating conditions.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. **Safety First**: Disconnect all AC input power to the drive. Wait for the DC bus voltage (measure at DC+/DC- terminals) to discharge below 50VDC before proceeding.

  2. 2

    2. Disconnect the motor cables from the drive output terminals (U/T1, V/T2, W/T3).

  3. 3

    3. With the motor disconnected, perform a static check (diode test with a multimeter) on the drive's output IGBTs (between DC+ and U, V, W; and DC- and U, V, W) as per the drive service manual to identify shorted power devices.

  4. 4

    4. Visually inspect the DC bus fuse (typically located near the rectifier or DC link) for signs of opening. If an external fuse, check its continuity with a multimeter.

  5. 5

    5. If IGBTs are confirmed faulty, the power module or the entire drive likely needs replacement. Replacing the fuse without addressing the underlying short circuit will result in immediate re-fault.

  6. 6

    6. Before re-applying power after replacing any components, ensure motor insulation resistance (megger test) is good and motor cable integrity is verified.

Alle Codes in diesem Handbuch durchsuchen (64)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Yaskawa PUF DC Bus Fuse Open: Fehleranalyse & Ursachen | ErrorLib