DIAG_10 (Channel S1/S0 or S3/S2)

Short Circuit to Ground / Overload

Wago · PFC200 PLC

Was bedeutet DIAG_10 (Channel S1/S0 or S3/S2) ?

The diagnostic bits S1/S0 or S3/S2 for a digital output channel on module 75x-506 are set to '10'. This indicates either a short circuit exists between the output and ground or an overload condition on the output channel. This state protects the module from damage but prevents the output from operating.

Häufige Ursachen

  • A short circuit exists between the output terminal and ground.
  • The current drawn by the connected load exceeds the module's specified output current rating (overload).
  • A faulty load is causing excessive current draw.
  • Internal short within the wiring to the load.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Measure resistance between the affected output terminal and ground to detect a short circuit.

  2. 2

    Check the current drawn by the connected load and compare it to the module's specified output current rating.

  3. 3

    Disconnect the load from the module and verify if the diagnostic bits clear, then test the load separately.

  4. 4

    Inspect the wiring for any physical damage or insulation breakdown that could cause a short to ground.