Übersetzen...
7

MOL Contact Fault

Vacon · X4

Was bedeutet 7 ?

This fault occurs when the Motor Overload (MOL) digital input is activated, indicating an overload condition detected externally or a misconfiguration of the input logic. The MOL input acts as a safety interlock to protect the motor from damage due to excessive thermal or current loading.

Häufige Ursachen

  • External motor overload relay (connected to the MOL input) tripped due to an actual motor overload condition.
  • Incorrect configuration of the digital input assigned as MOL (e.g., parameter P0-19 DI Function) resulting in unintended activation.
  • Open circuit in the wiring to the MOL digital input, if configured as a normally closed (NC) contact.
  • Faulty external overload relay or wiring causing a false trip signal to the MOL input.
  • Contactor chatter or auxiliary contact bounce triggering the MOL input intermittently.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Inspect the external motor overload relay (thermal or electronic) for a tripped status indicator and reset it if necessary.

  2. 2

    2. Verify parameter P0-19 (DI Function) or similar parameter for the MOL input is correctly configured for the desired normally open (NO) or normally closed (NC) logic.

  3. 3

    3. Measure the continuity of the external MOL contact and its wiring back to the drive's digital input terminal to ensure a proper signal path.

  4. 4

    4. Check the motor's actual current draw using a clamp meter at the drive output (T1/U, T2/V, T3/W) to determine if a true overload condition exists (compare to P0-03).

  5. 5

    5. Temporarily bypass the MOL input by removing its wiring from the drive terminal (ensure safety procedures are followed) to confirm if the fault clears.

Alle Codes in diesem Handbuch durchsuchen (33)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes