Übersetzen...
22

Speed Reference Loss (Adv. Code 0)

Vacon · X4

Was bedeutet 22 ?

This fault occurs when the drive's configured analog input signal, typically for speed or frequency reference, falls below a specified minimum level set by customer parameters. This indicates a loss or degradation of the command signal, potentially leading to uncontrolled operation or shutdown. The drive cannot receive proper commands.

Häufige Ursachen

  • Analog input signal wire breakage or loose connection at drive terminals (e.g., AI1, GND) or signal source terminals.
  • External analog reference source (e.g., PLC analog output, potentiometer) malfunction or loss of its auxiliary power supply (e.g., 24VDC).
  • Drive parameter P3-01 (Analog Input Minimum) configured with a value higher than the actual lowest expected signal from the reference source.
  • Excessive electrical noise or electromagnetic interference (EMI) causing the analog signal to drop intermittently below the defined minimum threshold.
  • Internal fault on the drive's analog input circuit board or ADC converter, misinterpreting the actual input signal.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Measure the analog input voltage or current at the drive's input terminals (e.g., AI1 to GND for voltage) using a calibrated multimeter. Verify it is above the value set in parameter P3-01.

  2. 2

    Inspect the entire analog signal cable run from the source (e.g., PLC output terminal X3/1) to the drive's analog input terminals (e.g., A1, A2, A3) for continuity, secure connections, and proper shielding.

  3. 3

    Verify the external analog signal source (e.g., PLC analog output module) is functioning correctly by measuring its output signal directly at its terminals.

  4. 4

    Review drive parameters P3-01 (Analog Input Minimum) and P3-02 (Analog Input Max) to ensure they are set appropriately for the nominal range of the input signal (e.g., 0-10VDC, 4-20mA).

  5. 5

    If an external potentiometer is used, measure its resistance across its terminals and test its voltage output stability across its full rotational range.

Alle Codes in diesem Handbuch durchsuchen (33)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes