Übersetzen...
15

Dynamic Brake Circuit Fault (Power-up, Adv. Code 3,4,5)

Vacon · X4

Was bedeutet 15 ?

This fault indicates a general malfunction within the Dynamic Braking (DB) circuit detected immediately upon drive power-up, and it is not auto-resettable. This suggests a significant internal component failure or wiring issue within the braking chopper or its control. This fault prevents the drive from starting and operating safely.

Häufige Ursachen

  • Internal dynamic braking (DB) IGBT failure (e.g., short circuit or open circuit), detected during the drive's power-up self-test sequence.
  • External dynamic braking resistor (DBR) is short-circuited or has significantly lower resistance than specified, causing an overcurrent condition upon internal activation.
  • Open circuit in the dynamic braking resistor circuit (e.g., cable breakage to DBR, faulty DBR element), preventing proper current path detection by the drive.
  • Drive's internal gate driver circuit fault for the dynamic braking IGBT, preventing correct switching or current sensing.
  • Incorrectly rated or specified DBR connected, leading to current sensing discrepancies that trigger the fault upon power-up diagnostics.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Power down the drive and wait for the DC bus voltage to discharge below 45VDC (verify with multimeter on DC+ and DC- terminals).

  2. 2

    Disconnect the external dynamic braking resistor (DBR) from the drive's B1 and B2 terminals.

  3. 3

    Measure the resistance of the disconnected DBR across its terminals using an ohmmeter. Compare the reading to the manufacturer's specified resistance value (e.g., 50 Ohms).

  4. 4

    With the DBR disconnected, re-apply power to the drive and observe if the fault clears. If it does, the DBR or its connecting cables are suspect.

  5. 5

    If the fault persists with the DBR disconnected, it indicates an internal drive component failure related to the DB circuit, requiring service or replacement of the drive unit.

Alle Codes in diesem Handbuch durchsuchen (33)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes