Übersetzen...
F83

Safe Stop

Vacon · NXP AFE-II Drive

Was bedeutet F83 ?

This fault is triggered by a digital input, indicating that a safe stop command or condition has been activated from an external device. This is a critical safety interlock.

Häufige Ursachen

  • Activation of an emergency stop button (E-Stop) connected to a dedicated safety input (e.g., STO input, Safe Stop DI).
  • Triggering of a safety light curtain, safety scanner, or safety gate switch connected to the drive's safe stop input.
  • Fault condition detected by an external safety relay or safety PLC, which then deactivates the safe stop input signal.
  • Loss of a critical enabling signal (e.g., 24VDC Safe Enable) to the drive's safety circuit, leading to a safe stop state.
  • Broken or shorted wiring on the safe stop input circuit (e.g., between STO1, STO2, or safe DI) causing an unintended activation.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Identify the specific external safety device (e.g., E-Stop, light curtain) connected to the drive's safe stop input (e.g., STO terminals).

  2. 2

    Visually inspect and reset all active safety devices in the system to ensure they are in their safe, non-tripped state.

  3. 3

    Measure the voltage at the drive's safe stop input terminals (e.g., STO1, STO2 or Safe DI to COM) to verify the expected input signal.

  4. 4

    Verify the integrity of the safety circuit wiring, including cable continuity and terminal connections, from the safety device to the drive.

  5. 5

    Check diagnostic LEDs on any connected safety relays or safety PLCs for fault codes or status indications.

  6. 6

    Review parameter settings related to safe stop configuration (e.g., P7-01 for Safe Torque Off function) to ensure correct setup.

Alle Codes in diesem Handbuch durchsuchen (34)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes