Overcurrent
Vacon · 20 Compact
Was bedeutet 1 ?
The frequency converter has detected a motor current exceeding four times the nominal current (>4*IN) in the motor cable. This condition typically results from a sudden heavy increase in motor load, a short circuit in the motor cables, or the use of an unsuitable motor for the application, posing a risk of damage to the motor or drive.
Häufige Ursachen
- Motor draws excessive current.
- Short circuit in motor windings or cables.
- Mechanical overload or jamming.
- Rapid acceleration or deceleration ramps (P1-16, P1-17).
- Output voltage too low relative to motor speed.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Check the motor loading to ensure it is within the rated capacity of the drive and motor.
- 2
Verify the motor size matches the application requirements and the frequency converter specifications.
- 3
Inspect all motor cables for any signs of physical damage, insulation breakdown, or short circuits between phases or to ground.