Übersetzen...
F01611

SI P1 (CU): Defect in a monitoring channel

Siemens · SINAMICS G120C Variable Speed Drive

Was bedeutet F01611 ?

The drive-integrated "Safety Integrated" function on processor 1 has detected a fault in the crosswise data comparison between its two monitoring channels, initiating a STOP F. This often leads to fault F01600 as a subsequent response. A defect in a safety monitoring channel is a critical safety system failure that must be resolved to ensure the safe operation of the machine and compliance with safety standards.

Häufige Ursachen

  • Internal hardware fault within the Safety Integrated module, leading to a discrepancy between the two monitoring channels.
  • Excessive electromagnetic interference (EMI) affecting the internal communication paths of the safety processor.
  • Firmware inconsistency or corruption within the Safety Integrated function, preventing proper cross-channel comparison.
  • Failure of an internal test pulse or a sensor feedback path within the dual-channel safety architecture.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check for strong EMI sources near the drive and its control unit. Relocate signal cables if they are routed too close to power cables.

  2. 2

    Perform a power cycle of the drive system (main power off/on) to reset the Safety Integrated module.

  3. 3

    Verify the firmware version of the control unit (r0018) against the recommended version for the installed safety option module.

  4. 4

    If the fault persists, consider replacing the control unit (CU) as an internal hardware defect is likely.

Alle Codes in diesem Handbuch durchsuchen (34)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Siemens SINAMICS G120C Variable Speed Drive