SI P1 (CU): STOP A initiated
Siemens · SINAMICS G120C Variable Speed Drive
Was bedeutet F01600 ?
The drive-integrated "Safety Integrated" function on processor 1 has detected an error and initiated a STOP A. This typically occurs due to an unsuccessful safety shutdown path check or as a consequence of F01611. This fault indicates a critical issue with the safety system, preventing drive operation and requiring immediate attention to ensure machine and personnel safety.
Häufige Ursachen
- Failed forced checking procedure (FCP) of the safety shutdown path, possibly due to a stuck contactor or relay in the safe output chain.
- External safety device (e.g., emergency stop button, safety gate switch) has activated, triggering the Safe Torque Off (STO) function.
- Cross-monitoring fault between internal safety processors, indicating a deviation in expected safe state within Safety Integrated.
- Incorrect wiring or loose connection to the Safety Integrated inputs (e.g., terminals X1, X2) causing an unintended safety state.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Verify the status of all connected external safety components (e.g., E-stop, safety light curtains, safety door switches) for activation.
- 2
Check the wiring integrity of the safety circuit, specifically the connections to the STO inputs (e.g., X1, X2 terminals on safety module).
- 3
Review the drive's safety log (r9700) for specific details on the triggering event and the status of internal safety signals.
- 4
Initiate a forced checking procedure (FCP) via parameter P9500 to confirm the functionality of the safety output path.