F01630

Brake control defective

Siemens · SINAMICS G120

Was bedeutet F01630 ?

The motor holding brake control is malfunctioning, posing a risk of uncontrolled motor movement. This can stem from an incorrect p1278 setting, disconnected or interrupted brake cables, a ground fault, or a short-circuit in the brake winding. A fault in the Safe Brake Relay, Control Unit, or Power Module could also be the cause.

Häufige Ursachen

  • Incorrect setting of parameter P1278 (Brake control mode) for the specific motor or application.
  • Interruption or disconnection of the motor brake control cables (e.g., terminals X11/X12 or specific brake module connections).
  • Ground fault in the motor brake winding or its supply cabling.
  • Failure of the internal brake control relay or solid-state switch within the drive module.
  • Overcurrent or short circuit detected in the brake power supply circuit.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify the setting of parameter P1278 (Brake control mode) according to the motor's technical specifications and the application's requirements.

  2. 2

    Measure the resistance of the motor brake coil directly at the drive's brake terminals (e.g., X11/X12) to compare with the specified value (e.g., 20-50 Ohms).

  3. 3

    Check for 24VDC or 400VAC (depending on brake type) output voltage at the brake terminals when the drive commands brake release (e.g., using a multimeter).

  4. 4

    Inspect the entire brake cabling path from the drive to the motor for signs of physical damage, loose connections, or insulation breakdown.

  5. 5

    Perform an insulation resistance test (Megger test) on the brake cables and motor brake coil to detect ground faults.