Sign-of-life error in the Safety data
Siemens · SINAMICS G120
Was bedeutet F01625 ?
An error has occurred with the safety data's sign-of-life signal, indicating a potential communication or integrity issue within the safety functions. This can be caused by EMC disturbances or an inadmissible voltage at a Control Unit digital output. Such an error critically impacts the system's ability to maintain safe operation.
Häufige Ursachen
- Electromagnetic compatibility (EMC) interference affecting the safety communication bus or internal Control Unit communication.
- Incorrect or inadequate shielding of safety communication cables (e.g., PROFIsafe line).
- Processor overload or internal timing issues within the Control Unit preventing timely processing of safety sign-of-life signals.
- Temporary communication disruption between the safety Control Unit and the safety application (e.g., Safety CPU).
- Inconsistent safety configuration data (e.g., checksum mismatch) between the drive and the higher-level safety controller.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Inspect and verify the shielding termination for all safety communication cables (e.g., PROFINET/PROFIBUS) at both the drive and controller ends.
- 2
Check for potential sources of high-frequency interference (e.g., unsuppressed contactors, welding equipment) near the drive or safety communication lines.
- 3
Verify the drive's firmware version is compatible with the safety PLC firmware and the configured safety functions.
- 4
Perform a power cycle of the drive and the associated safety controller to re-initialize communication.
- 5
Review event logs (e.g., drive fault memory and safety PLC diagnostic buffer) for concurrent communication issues or other related faults.