Was bedeutet F01600 ?

A STOP A request has been initiated, often due to a safety-related event such as defective hardware, incorrect STO configuration, or a discrepancy at STO terminals. This condition is indicated by fault value r0949 and results in an immediate, uncontrolled cessation of motor power. It is a critical fault impacting machine safety and operation.

Häufige Ursachen

  • Failure of an external safety component connected to the STO circuit (e.g., emergency stop button, safety gate switch).
  • Incorrect parameterization of Safety Integrated functions, specifically STO (Safe Torque Off), like P9501 not configured correctly for the application.
  • Discrepancy detected between the two STO input channels (F-DI1 and F-DI2) indicating a potential wiring fault or internal hardware issue.
  • Internal hardware defect within the Control Unit's safety monitoring circuitry.
  • External safety relay output contacts (connected to F-DI1/F-DI2) opening asynchronously.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Measure the voltage across STO input terminals (e.g., X124/1 and X124/2 for F-DI1, X124/3 and X124/4 for F-DI2) with a multimeter to verify an active "1" signal (24VDC) when STO is not active.

  2. 2

    Verify the integrity of all external safety components in the STO circuit (e.g., E-stop buttons, safety light curtains) by actuating them and observing their electrical state.

  3. 3

    Check the parameter P9501 (Safety Integrated function selection) to ensure STO is correctly enabled or disabled according to the system's safety concept.

  4. 4

    Inspect the wiring for the STO input channels (e.g., terminals X124/1 through X124/4) for loose connections, insulation damage, or short circuits.

  5. 5

    Execute a safety function test (e.g., using P9700=1 to reset) after verifying external safety circuit integrity and parameter settings.