Übersetzen...
F00060

Asic Timeout

Siemens · SINAMICS G120

Was bedeutet F00060 ?

An internal communication failure between the inverter's power module and control unit has occurred, indicated by an ASIC timeout. This can be caused by loose connections, electromagnetic interference (EMC), or a faulty internal component, leading to a loss of control and drive shutdown, impacting operational reliability.

Häufige Ursachen

  • Loose or corroded ribbon cable connection between the control unit and the power module (e.g., X121, X122 connectors).
  • Heavy electromagnetic interference (EMI) disrupting internal communication signals (e.g., from unshielded power cables, poor grounding).
  • Faulty control unit (CU) or power module (PM) preventing proper ASIC communication.
  • Damage to the internal communication bus or ASIC chip on either the control unit or power module.
  • Insufficient auxiliary power supply to the control unit or communication ASICs.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    De-energize the drive and ensure the control unit is securely seated and locked into the power module chassis.

  2. 2

    Carefully inspect and re-seat all internal ribbon cables (e.g., between CU and PM) for firm connection and no visible damage.

  3. 3

    Check the drive's grounding connections (e.g., main PE terminal) to ensure effective EMI suppression.

  4. 4

    Measure the auxiliary power supply voltages (e.g., 24VDC, 5VDC) on the control unit for stability and correct levels.

  5. 5

    Isolate the drive from potential external EMI sources by checking cable routing and shielding integrity.

Alle Codes in diesem Handbuch durchsuchen (109)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes