Übersetzen...
F07011

Drive: Motor overtemperature

Siemens · DCM

Was bedeutet F07011 ?

The motor has exceeded its programmed temperature fault threshold, or the I2t thermal model indicates overtemperature. This can be caused by motor overload, high ambient temperature, or issues with the temperature sensor itself (wire breakage, incorrect connection). Prolonged overtemperature risks permanent motor damage.

Häufige Ursachen

  • Continuous mechanical overload on the motor shaft, causing excessive current draw and heat generation.
  • Insufficient motor cooling due to blocked fan fins, accumulated dust on the motor housing, or a failed external cooling fan.
  • High ambient temperature around the motor, exceeding its specified operating limits (e.g., 40°C).
  • Incorrect motor data entered into the drive parameters (e.g., P1-04, P1-05), leading to an inaccurate I2t thermal model.
  • Failure of the motor's internal temperature sensor (e.g., PTC, KTY, PT100) or its wiring, providing an erroneous high reading.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Measure the surface temperature of the motor housing (e.g., at cooling fins, bearing shields) using an infrared thermometer.

  2. 2

    Inspect the motor's cooling fan (if present) for proper rotation, and clean cooling fins or air passages of dust/debris.

  3. 3

    Verify the actual mechanical load on the motor shaft against the motor's rated torque (e.g., check for binding in driven machine).

  4. 4

    Check drive parameters P1-04 (Motor rated current), P1-05 (Motor rated speed), and P1-06 (Motor rated voltage) against the motor nameplate.

  5. 5

    Measure the resistance of the motor's temperature sensor at the drive's sensor input terminals (e.g., X2-2, X2-3) and compare to the sensor datasheet.

  6. 6

    Monitor the motor current (e.g., Parameter P2-01) under normal operating conditions and compare it to the motor's rated current (P1-04).

Alle Codes in diesem Handbuch durchsuchen (60)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes