Übersetzen...
A07852

External alarm 3

Siemens · DCM

Was bedeutet A07852 ?

The BICO signal for 'external alarm 3' was triggered, indicating that the predefined condition for this alarm has been met. This is a user-configurable alarm tied to an external event, sensor, or logic input. The specific cause is defined by parameter p2117.

Häufige Ursachen

  • Input signal connected to parameter P2102 (External alarm 3 trigger) transitioned from 0 to 1, indicating a tripped safety interlock or sensor.
  • A process limit switch (e.g., high-level sensor, over-pressure switch) wired to a digital input, which is mapped to P2102.
  • A PLC output controlling an external warning condition, mapped to the drive's digital input and subsequently linked via BICO to P2102.
  • An over-temperature switch on an external motor or bearing, wired to the drive's digital input to trigger the alarm.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Identify the digital input (e.g., DI0, DI1) that is BICO-connected to parameter P2102 (External alarm 3 trigger).

  2. 2

    2. Monitor the status of the identified digital input using parameter r0722[x] (e.g., r0722[0] for DI0) to verify its current state.

  3. 3

    3. Trace the physical wiring from the identified digital input back to its source (e.g., limit switch, sensor, PLC output).

  4. 4

    4. Inspect the external sensor or switch for its activated state; for example, check if a pressure switch has exceeded its setpoint.

  5. 5

    5. Verify the logic and configuration of the external device causing the alarm, ensuring its operating limits are appropriate for the application.

Alle Codes in diesem Handbuch durchsuchen (60)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes