F04
Brake chopper
SEW Eurodrive · MOVITRAC 07B System
Was bedeutet F04 ?
An immediate switch-off with inhibit due to issues with the brake chopper. This can be caused by excessive regenerative power, an interrupted or short-circuited braking resistor circuit, an improperly high braking resistance, a defective brake chopper, or a ground fault.
Häufige Ursachen
- Too much regenerative power
- Braking resistor circuit interrupted
- Short circuit in the braking resistor circuit
- Braking resistance too high
- Brake chopper defective
- Ground fault
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Extend deceleration ramps to reduce regenerative power
- 2
Check the supply cable to the braking resistor for continuity
- 3
Rectify any short circuit detected in the braking resistor circuit
- 4
Check the technical data of the braking resistor to ensure correct value
- 5
Eliminate any ground fault detected