Übersetzen...
08

Speed Monitoring Tripped

SEW Eurodrive · MOVIMOT MM..C

Was bedeutet 08 ?

The MOVIMOT® signals a fault (red LED flashing slowly) if the drive operates at its current limit for more than 1 second while speed monitoring is active. The current limit must be continuously attained for the duration of a pre-set delay time before this monitoring function responds. This indicates a sustained overload condition or a blockage that prevents the motor from reaching its commanded speed.

Häufige Ursachen

  • Drive operated at the current limit for more than 1 second.
  • Speed monitoring is active (DIP switch S2/4 ON for standard design or S4/2 ON for AS-Interface design).
  • Mechanical blockage or excessive load preventing the motor from moving freely.
  • Motor stalled or operating significantly below commanded speed due to high resistance.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify the status of the speed monitoring DIP switch: for standard design, check S2/4; for AS-Interface, check S4/2. If speed monitoring is not required, set the relevant DIP switch to OFF.

  2. 2

    Inspect the mechanical system for obstructions, excessive friction, or damage that could impede motor rotation.

  3. 3

    Measure motor current during operation to determine if it consistently hits the current limit.

  4. 4

    Check the mechanical load on the motor and ensure it is within the drive's continuous operating capacity.

  5. 5

    Review acceleration and deceleration ramp times; excessively short ramps can cause transient current limit excursions.

Alle Codes in diesem Handbuch durchsuchen (21)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes