F14.21

SSI error bit

SEW Eurodrive · MOVIDRIVE system

Was bedeutet F14.21 ?

An error bit has been set in the SSI protocol by Encoder 2, indicating a data or communication problem. This can result from incorrect startup parameters, encoder settings, wiring issues, or external interference, affecting position feedback reliability.

Häufige Ursachen

  • Mismatch between the SSI resolution (P3-55) or number of turns (P3-56) configured in the drive for Encoder 2 and the actual encoder specifications.
  • Intermittent electrical noise on the SSI data or clock lines, potentially due to inductive loads or unshielded cables running parallel to power cables.
  • Minor internal malfunction within Encoder 2, causing occasional setting of non-critical error bits in the SSI telegram.
  • Ground loop issues affecting the SSI signal integrity, potentially caused by multiple grounding points or incorrect earthing practices.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Cross-reference drive parameters P3-55 (SSI resolution for Encoder 2) and P3-56 (SSI number of turns for Encoder 2) against the Encoder 2 datasheet and adjust if necessary.

  2. 2

    Visually inspect the routing of the Encoder 2 cable to ensure it is separated from high-current power cables and that shielding is continuous.

  3. 3

    Capture SSI clock and data signals at drive terminal X2 using an oscilloscope to identify any transient noise or signal distortions.

  4. 4

    Perform a resistance check on all SSI signal lines (CLOCK+, CLOCK-, DATA+, DATA-) and ground connection from drive terminal X2 to encoder connector.

  5. 5

    Reset the Encoder 2 configuration parameters in the drive (e.g., P3-50 to default) and reconfigure carefully.