Resolver 14-bit
SEW Eurodrive · MOVIDRIVE compact System (MCF/MCV/MCS4_A)
Was bedeutet 12 ?
Emergency stop occurs because 14-bit resolver evaluation is active, and the actual motor speed exceeds 3600 1/min. The resolver feedback system is not designed for accurate operation above this speed.
Häufige Ursachen
- The resolver feedback system is not providing valid or consistent positional data.
- Faulty resolver or resolver interface board.
- Signal interference or connection issues with the resolver wiring.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Set parameter P302 (Maximum speed 1) to a maximum value of 3600 1/min.