Übersetzen...
F-34

Ramp timeout

SEW Eurodrive · MCBSM

Was bedeutet F-34 ?

The drive has exceeded its set stop ramp time, meaning it took longer than programmed to decelerate and come to a stop. This fault triggers an immediate switch-off with inhibit, often due to insufficient ramp time settings relative to the load or braking capability. This can result in poor control and mechanical stress if not corrected.

Häufige Ursachen

  • Deceleration ramp time (Parameter P1-13) set too short for the inertia of the connected mechanical load, making physical deceleration impossible within the timeframe.
  • Insufficient braking torque available from the motor or an external braking resistor (Parameter P2-22, Brake resistor resistance) that is too high or disconnected.
  • Mechanical binding or excessive friction in the load (e.g., conveyor belt jammed, gearbox fault) preventing smooth deceleration.
  • Incorrect motor data (e.g., P1-01, Motor rated power; P1-02, Motor rated frequency) entered into the drive, leading to miscalculation of braking capacity.
  • Regenerative energy from the load exceeding the drive's or braking resistor's dissipation capacity, causing DC bus overvoltage during deceleration.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Increase the deceleration ramp time (Parameter P1-13) in small increments (e.g., 10-20%) and retest the stop command to see if the fault clears.

  2. 2

    Check the DC bus voltage (Monitor UDC) during deceleration for spikes. If present, inspect the external braking resistor connections and measure its resistance value to verify it matches Parameter P2-22.

  3. 3

    Manually attempt to rotate the mechanical load (with power disconnected and locked out) to check for binding, excessive friction, or mechanical damage that would impede deceleration.

  4. 4

    Verify all motor nameplate data (P1-01, Motor rated power; P1-02, Motor rated frequency; P1-03, Motor rated voltage; P1-04, Motor rated current; P1-05, Motor rated speed) are correctly entered into the drive.

  5. 5

    Confirm the motor's braking torque capability is sufficient for the application's inertia, considering the drive's current limits during regeneration.

  6. 6

    If the problem persists with a correctly sized braking resistor and adjusted ramp times, consider using a controlled stop function (e.g., DC injection braking) or a larger braking resistor solution.

Alle Codes in diesem Handbuch durchsuchen (50)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes