91

Communication timeout bus module – MOVIMOT®

SEW Eurodrive · Drives

Was bedeutet 91 ?

The communications link between the fieldbus interface (MFP/MFI) and the MOVIMOT® inverter is interrupted or experiences a timeout. This system fault is signaled to the PLC as error code 91 dec via the diagnostics channel or status words, and typically triggers a steady 'SYS-F' LED light on the fieldbus interface.

Häufige Ursachen

  • Interrupted or faulty electrical communication link between the fieldbus interface (MFP/MFI) and the MOVIMOT® inverter.
  • Missing 24 V supply to the MOVIMOT® inverter.
  • Maintenance switch on the field distributor is set to OFF.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check and re-establish the electrical communication link between the fieldbus interface (MFP/MFI) and the MOVIMOT® inverter (e.g., verify connections at terminals RS+ and RS-).

  2. 2

    Verify the 24 V electronics supply voltage to the MOVIMOT® inverter.

  3. 3

    Check the setting of the maintenance switch on the field distributor to ensure it is in the ON position.

Alle Codes in diesem Handbuch durchsuchen (39)