FCF2

Output Contactor Open

Schneider Electric · Altivar Machine ATV320 Variable Speed Drive

Was bedeutet FCF2 ?

Indicates that the output contactor is detected as open when it should be closed. This prevents the drive from supplying power to the motor, resulting in a failure to start or operate. This could be due to a wiring issue, contactor fault, or an active interlock.

Häufige Ursachen

  • The output contactor fails to close when commanded.
  • Insufficient voltage or current to energize the contactor coil.
  • Mechanical obstruction preventing the contactor from engaging.
  • Faulty control signal (e.g., from P2-10) commanding the contactor to close.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify control wiring to the output contactor coil for continuity and correct voltage.

  2. 2

    Check the output contactor for mechanical damage, an open coil circuit, or burnt contacts.

  3. 3

    Ensure all safety interlocks or permissive conditions for contactor closure are met.

  4. 4

    Measure the voltage supplied to the contactor coil when it should be energized.