Übersetzen...
ObF

Overvoltage During Deceleration

Schneider Electric · ALTIVAR 28 Variable Speed Drive

Was bedeutet ObF ?

This fault occurs when the DC bus voltage rises above its safe limit during motor deceleration, typically due to kinetic energy being regenerated back to the drive from a sudden stop or an overhauling load. Without proper energy dissipation, this can damage the drive's DC bus components.

Häufige Ursachen

  • Deceleration ramp time (Parameter P0-12) set too short for the load's inertia, causing rapid energy regeneration.
  • Overhauling load condition (e.g., gravity-fed conveyor, fan stopping) generating kinetic energy back to the drive.
  • Dynamic Braking Resistor (DBR) is not connected, undersized, or has failed (open circuit).
  • Dynamic Braking Chopper (internal or external) is faulty or not enabled (Parameter P1-10 or similar).
  • Excessive regeneration due to frequent starts and stops with high inertia loads.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Increase deceleration ramp time (Parameter P0-12) by 20% and retest.

  2. 2

    2. Verify the dynamic braking resistor (DBR) connection between terminals BR+ and BR- (or similar) is secure.

  3. 3

    3. Measure the resistance of the DBR (power off) and compare it to the specified value in the drive manual.

  4. 4

    4. Confirm the braking function is enabled in drive parameters (e.g., P1-10 for braking resistor type or chopper enable).

  5. 5

    5. Check for overhauling load conditions; consider mechanical brakes or larger braking resistor if load is inherently regenerative.

Alle Codes in diesem Handbuch durchsuchen (13)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Schneider Electric ALTIVAR 28 Variable Speed Drive