Cross-circuit in Sensor Circuit 1

Phoenix Contact · ib il safe 2-eco

Was bedeutet 3 ?

A cross-circuit has been detected in sensor circuit 1, indicated by active cross-circuit detection. This condition occurs while sensor circuit 2 is active, the reset/start circuit is activated, and the segment circuit is open. This type of error can compromise the functional safety of the device by providing incorrect sensor input information.

Häufige Ursachen

  • Cross-circuit detected within sensor circuit 1

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Switch off the operating voltage to the device

  2. 2

    Identify and physically remove the cross-circuit in sensor circuit 1

  3. 3

    Perform a function test to verify correct device operation