Übersetzen...
902

POWER SUPPLY FAULT

Otis · DSD 412 DC Elevator Drive

Was bedeutet 902 ?

The Low Voltage Power Supply (A4) output has dropped below 60% of its rated voltage, leading to a drive shutdown. A CPU Reset is required after the cause of the fault has been rectified.

Häufige Ursachen

  • Loss of 115V AC input power to the A4 power supply.
  • Short circuits present in the +5V, +/-15V, or +24V circuits, potentially external to the drive itself.
  • Failure of the A4 Power Supply module.
  • A blown fuse located internally within the A4 power supply.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify the presence of 115V AC input power to the A4 board.

  2. 2

    Check for short circuits in the +5V, +/-15V, and +24V circuits, inspecting both internal and external connections.

  3. 3

    Inspect any internal fuses of the A4 power supply for continuity and replace if blown.

  4. 4

    If all other causes are ruled out, replace the A4 Power Supply PCB.

  5. 5

    Perform a CPU reset on the Drive Control PCB after addressing the fault.

Alle Codes in diesem Handbuch durchsuchen (48)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Otis DSD 412 DC Elevator Drive