Übersetzen...
402
LOOP CONTACTOR FAULT
Otis · DSD 412 DC Elevator Drive
Was bedeutet 402 ?
The Loop Contactor auxiliary contact failed to pick up or drop out within the designated time, as requested by the DSD 412 drive. The detection time is set by Function #102, which can be 450ms or 3 seconds.
Häufige Ursachen
- Defective Loop Contactor Auxiliary contact (check feedback at TB1-7).
- Defective Contactor (open coil or mechanical binding).
- Defective Pilot Relay LPR.
- Interference from other elevator relay contact circuits.
- Function #102 not set correctly for contactor type (e.g., small vs. large HP drives).
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Check for proper feedback at TB1-7 for the Loop Contactor Aux contact.
- 2
Check the contactor for an open coil or mechanical binding.
- 3
Check the Pilot Relay LPR for defects.
- 4
Identify and resolve interference from other elevator relay contact circuits.
- 5
If using large contactors with large HP drives, set Function #102 to 1 (On) for a 3-second fault detection time; otherwise, set to 0 (Off) for 450ms.
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026
Verwandte Fehlercodes
Quelle: Otis DSD 412 DC Elevator Drive