Übersetzen...
A409.00 to A409.03

Expansion Rack Address Duplication

Omron · SYSMAC CJ2 CPU Unit

Was bedeutet A409.00 to A409.03 ?

This flag turns ON when an Expansion Rack's starting word address, set in CX-Programmer, either overlaps with another Rack's allocation or exceeds the maximum address CIO 0901. Bits 00 to 03 correspond to Racks 0 to 3. The CPU Unit operation will stop and the ERR/ALM indicator on the front of the CPU Unit will light.

Häufige Ursachen

  • Two different Expansion Racks are configured with overlapping starting word addresses in the I/O Table
  • An Expansion Rack's starting address is set higher than CIO 0901, which is outside the permissible range

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Identify the affected Expansion Rack(s) by checking the ON status of A409.00 to A409.03 (Bits 00-03 for Racks 0-3)

  2. 2

    Access the PLC Setup or I/O Table in CX-Programmer to review the starting word addresses for all Expansion Racks

  3. 3

    Reconfigure the starting word addresses to ensure no overlap between Racks

  4. 4

    Adjust the starting word address of the problematic Rack to be within the valid range (i.e., not exceeding CIO 0901)

Alle Codes in diesem Handbuch durchsuchen (27)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes