Übersetzen...
A402.06

Special I/O Unit Data Exchange Error

Omron · SYSMAC CJ2 CPU Unit

Was bedeutet A402.06 ?

This fault indicates an error during data exchange between the CPU Unit and a Special I/O Unit. When this error occurs, the Special I/O Unit Error Flag (A402.06) is turned ON. The corresponding bit for the unit number (0-95) in A418 to A423 will also be set. The CPU Unit will continue operating, and the ERR/ALM indicator on the front of the CPU Unit will flash.

Häufige Ursachen

  • Communication failure during data exchange with a Special I/O Unit (unit numbers 0-95).
  • Physical connection issue with the Special I/O Unit.
  • Faulty Special I/O Unit.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Identify the faulty Special I/O Unit by checking the status of bits A418.00 to A423.15.

  2. 2

    Inspect the physical connection and bus cables of the identified Special I/O Unit.

  3. 3

    Verify the power supply to the Special I/O Unit.

  4. 4

    Clear the error flag (A402.06) once the error condition is resolved.

Alle Codes in diesem Handbuch durchsuchen (27)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes