EtherCAT Slave Communications Error
Omron · NJ/NY-series NC Integrated Controller
Was bedeutet 87800000 hex ?
An error occurred in communication with an EtherCAT slave or NX unit assigned to a CNC motor of the CNC Function Module. This also triggers an error in the EtherCAT Master Function Module. The CNC motor with the error will have its SERVO OFF, and operations other than error reset are rejected. Additionally, the CNC motor will be placed in an undefined home state.
Häufige Ursachen
- Communication error with an EtherCAT slave or NX unit assigned to a CNC motor of the CNC Function Module.
- Communication error in at least one device when multiple devices are assigned to a single CNC motor.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Inspect EtherCAT communication cables (IN/OUT) for the affected slave (NX unit or CNC motor amplifier) for physical damage, proper routing, and secure connections at both ends.
- 2
Verify the auxiliary power supply voltage to the affected EtherCAT slave unit and the CNC motor amplifier, ensuring it meets the specified requirements.
- 3
Observe the EtherCAT status indicators on both the NJ/NY Master and the affected EtherCAT slave for diagnostic codes or link status.
- 4
Check the EtherCAT network configuration in Omron Sysmac Studio, confirming the affected slave's node address, device type, and cyclic data mapping are correct.