54015601 hex

Deceleration Setting Out of Range

Omron · NJ/NX-series Machine Automation Controller

Was bedeutet 54015601 hex ?

The parameter specified for the Deceleration input variable to a CNC instruction is out of range. This occurs when an instruction input parameter exceeds its valid numerical limits.

Häufige Ursachen

  • Instruction input parameter exceeded the valid range of the input variable.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify the specific CNC instruction and the Deceleration input variable causing the error within the Omron Sysmac Studio project.

  2. 2

    Inspect the current value assigned to the Deceleration input variable and compare it against the valid numerical range specified in the instruction's help or the associated axis settings.

  3. 3

    Check the configured Deceleration limits for the affected axis in the Omron NJ/NX controller's axis settings to ensure they encompass the required operational range.

  4. 4

    Adjust the Deceleration input variable's value or the axis's Deceleration limit within Sysmac Studio to be within the permissible operating range defined by the system specifications.