Was bedeutet 08180000 hex ?

Initialization of internal position data was not processed correctly in Fully-closed Control Mode and Absolute Value Mode. This is similar to the internal encoder error but specific to external encoders used in fully-closed loop systems.

Häufige Ursachen

  • There is insufficient power supply voltage for the external encoder.
  • Noise is entering on the external encoder line.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify the external encoder's power supply voltage at the encoder terminals and controller input against manufacturer specifications.

  2. 2

    Inspect all external encoder cabling for physical damage, proper routing, secure connections, and correct shielding termination at both the encoder and controller ends.

  3. 3

    Check Omron Sysmac Studio for correct external encoder module configuration, associated axis parameters (e.g., resolution, scaling, data format), and fully-closed loop settings.

  4. 4

    Perform a controlled power cycle of the Omron NJ/NX controller and associated servo system to force a fresh re-initialization of all connected devices.