STO Self-diagnosis Error
Omron · MX2 Series Type V2 Compact Inverter
Was bedeutet E99. ?
This error indicates an internal fault within the inverter's STO (Safe Torque Off) input terminal or its internal safety circuit. This is a critical internal diagnostic failure, signaling that the inverter's safety function itself is not operating normally. It does not depend on the GS input operation selection, implying a fundamental issue with the safety hardware.
Häufige Ursachen
- Short circuit or open circuit detected on the STO input terminals (e.g., S1/S2, or X3:STOA/STOB).
- Internal failure of the inverter's safety monitoring circuit components (e.g., safety relays, monitoring ICs).
- External wiring fault to the STO inputs, such as incorrect cabling to a safety relay or PLC safety output.
- Discrepancy detected between redundant STO input channels (e.g., S1 and S2 signals are not coherent).
- Transient voltage spike or electromagnetic interference (EMI) affecting the sensitive internal safety circuit.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
1. Power off the inverter, disconnect all wiring from the STO terminals (e.g., S1/S2 or X3:STOA/STOB), and re-apply power to check for internal fault.
- 2
2. If the fault clears with STO terminals disconnected, perform a continuity test on all external STO wiring, checking for shorts or opens.
- 3
3. If an external safety device is used, bypass it temporarily with a wired jumper (e.g., short S1 to SINK and S2 to SINK, referring to manual's STO wiring diagram) to isolate the external circuit.
- 4
4. Measure the voltage across STO input terminals (e.g., S1-SINK and S2-SINK) to ensure appropriate signal levels (e.g., 24VDC or 0VDC) from the safety source.
- 5
5. If the fault persists after verifying external wiring and bypassing, the inverter's internal safety circuit has failed and requires unit replacement.
- 6
6. Ensure proper grounding of the inverter and shielded cabling for STO inputs to mitigate EMI effects.