Übersetzen...
22 hex

Modbus Exception: Function Not Allowed (Inverter State Specific)

Omron · MX2 Series Type V2 Compact Inverter

Was bedeutet 22 hex ?

This Modbus exception indicates that the inverter cannot perform the requested function due to its current operating state or configuration. This includes attempts to change RUN-protected parameters during operation, issue an Enter command while the inverter is in RUN or trip status, write to soft-locked or password-protected registers, or modify fixed I/O terminal settings. It's a broad category of operational constraints.

Häufige Ursachen

  • Attempting to write to a parameter (holding register) that is only modifiable when the inverter is in a specific state (e.g., STOP state for motor tuning parameters).
  • Trying to initiate a RUN command (e.g., FC06 to a control word register) when the inverter is already in RUN or in a fault state.
  • Attempting to clear a fault (e.g., writing 1 to a fault reset register) when the underlying fault condition still exists.
  • The requested function (e.g., certain diagnostic reads) is not available while the motor is running at high speed.
  • Inverter is in a protected mode (e.g., parameter lock, password-protected) preventing changes via Modbus.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Consult the inverter's manual to understand which parameters can only be modified in the STOP state and ensure the inverter is stopped before writing.

  2. 2

    2. Verify the inverter's current operating status (e.g., using a Modbus read on the status word register) before sending control commands or parameter writes.

  3. 3

    3. Ensure any faults are resolved (e.g., overcurrent condition removed, external trip reset) before attempting a fault reset via Modbus.

  4. 4

    4. Check for any active parameter lock or password protection settings in the inverter that prevent Modbus writes (e.g., P7-05 (Parameter Lock)).

  5. 5

    5. Sequence Modbus commands correctly: for example, stop the inverter, write parameters, then restart the inverter.

  6. 6

    6. Use a Modbus sniffer to observe the sequence of commands and inverter responses, correlating them with the inverter's actual state.

Alle Codes in diesem Handbuch durchsuchen (41)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Omron MX2 Series Type V2 Compact Inverter