CMND Instruction Command Format Error
Omron · MX2 Inverter RS-485 Connection Guide
Was bedeutet 10-04 ?
This error signifies that the command sent by the CMND instruction has an incorrect format or structure, preventing the communication unit from processing it correctly. This indicates a malformed FINS command, where the structure of the data sent does not comply with the expected protocol.
Häufige Ursachen
- Incorrectly formatted command data in the CMND instruction's 'S' operand (S: CIO 5020).
- Invalid or unsupported command code (S) specified for the communication unit.
- Mismatch between the number of command data bytes (C) and the actual data provided in the 'S' operand.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Review the setting contents of the first command word S (S: CIO 5020) and verify the Command code (S) is #2804 for Modbus-RTU communication.
- 2
Check the Number of command data bytes (C: CIO 5010) and ensure it accurately reflects the actual data length provided in the 'S' operand (e.g., #0008 for 8 bytes).
- 3
Cross-reference the FINS command structure with the CJ Series Communications Commands REFERENCE MANUAL (Cat. No. W342) if the command is non-standard.