Übersetzen...
A295.10
Illegal Access Error
Omron · CJ-series CJ2 CPU Unit
Was bedeutet A295.10 ?
An attempt was made to access memory in an unauthorized manner, and the PLC Setup is configured to stop operation on an instruction error, leading to a fatal program error (0x80F0). This includes reading/writing parameter areas, writing to non-installed memory, writing to an EM bank configured as EM file memory, writing to a read-only area, or using an indirect DM/EM address not in BCD when BCD mode is specified. The error address is output to A298/A299.
Häufige Ursachen
- Attempted reading/writing of a parameter area.
- Attempted writing to memory that is not physically installed.
- Attempted writing to an EM bank configured as EM file memory.
- Attempted writing to a read-only memory area.
- Indirect DM/EM address is not in BCD format when BCD mode is specified for addressing.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Identify the program address where the error occurred using A298 and A299.
- 2
Correct the instruction to ensure memory access is valid and authorized.
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026
Verwandte Fehlercodes
Quelle: Omron CJ-series CJ2 CPU Unit