A295.10

Illegal Access Error

Omron · CJ-series CJ2 CPU Unit

Was bedeutet A295.10 ?

An attempt was made to access memory in an unauthorized manner, and the PLC Setup is configured to stop operation on an instruction error, leading to a fatal program error (0x80F0). This includes reading/writing parameter areas, writing to non-installed memory, writing to an EM bank configured as EM file memory, writing to a read-only area, or using an indirect DM/EM address not in BCD when BCD mode is specified. The error address is output to A298/A299.

Häufige Ursachen

  • Attempted reading/writing of a parameter area.
  • Attempted writing to memory that is not physically installed.
  • Attempted writing to an EM bank configured as EM file memory.
  • Attempted writing to a read-only memory area.
  • Indirect DM/EM address is not in BCD format when BCD mode is specified for addressing.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Identify the program address where the error occurred using A298 and A299.

  2. 2

    Correct the instruction to ensure memory access is valid and authorized.