0x80EA
Expansion Rack Starting Word Address Exceeded
Omron · CJ-series CJ2 CPU Unit
Was bedeutet 0x80EA ?
An Expansion Rack's starting word address exceeds CIO 0901, preventing the CPU from correctly addressing the I/O for the rack. The corresponding bit in A409.00 to A409.03 (Racks 0 to 3) will be turned ON, indicating the affected rack.
Häufige Ursachen
- The first word setting for the Expansion Rack is configured above CIO 0900.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Check the first word setting for the Rack indicated by A409.00 to A409.03.
- 2
Using a Programming Device (e.g., CX-Programmer), change the setting to a valid word address below CIO 0900.