Übersetzen...
U6
Compressor Overcurrent (Overload) Cut-off
Mitsubishi Electric · R410A Systems
Was bedeutet U6 ?
The compressor has experienced an overcurrent condition due to an overload, leading to a safety cut-off. This could be caused by mechanical issues, excessively high head pressure, or an electrical fault within the compressor motor or associated circuit.
Häufige Ursachen
- Compressor overcurrent due to overload.
- Excessive mechanical load on the compressor.
- Thermal overload protection of the compressor tripped.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Measure compressor running current on all three phases using a clamp meter — compare measured values to the motor nameplate FLA.
- 2
Measure discharge and suction pressures to rule out high head pressure or liquid slugging as a cause.
- 3
Measure winding resistance of the compressor motor phases (U-V, V-W, U-W) and to ground using an ohmmeter — expect balanced resistance and no ground fault.
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026
Verwandte Fehlercodes
Quelle: Mitsubishi Electric R410A Systems