Übersetzen...
E16

Indoor Fan Motor Fault

Mitsubishi Electric · R410A Systems

Was bedeutet E16 ?

The indoor unit's fan motor is malfunctioning. This could be due to an electrical failure in the motor windings, seized bearings, or an issue with its control circuit, leading to insufficient airflow.

Häufige Ursachen

  • Indoor fan motor not rotating or running at incorrect speed.
  • Faulty motor winding or capacitor.
  • Obstruction preventing fan rotation.
  • Signal issue from the indoor fan control board.
  • Overcurrent protection tripped for the fan motor.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check the power supply voltage to the indoor fan motor terminals using a multimeter.

  2. 2

    Measure the resistance of the indoor fan motor windings (if accessible) — compare to specifications.

  3. 3

    Inspect the indoor fan motor for free rotation by hand (power off) and listen for unusual bearing noise.

  4. 4

    Verify the fan motor speed feedback signal at the indoor unit PCB.

Alle Codes in diesem Handbuch durchsuchen (60)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Mitsubishi Electric R410A Systems