U7

Too Low Superheat Due to Low Discharge Temperature

Mitsubishi Electric · PUZ-HA30/36NHA4 Outdoor Unit

Was bedeutet U7 ?

The system continuously detects discharge superheat less than or equal to -15°C [5°F] for 3 minutes, even with the linear expansion valve (LEV) at its minimum open pulse and the compressor running for 10 minutes. This indicates potential liquid floodback to the compressor, posing a significant risk of compressor damage.

Häufige Ursachen

  • Insufficient refrigerant charge.
  • Low discharge temperature leading to poor heat transfer.
  • Superheat setting too low for operating conditions.
  • Faulty discharge temperature sensor (e.g., P30).
  • Low suction pressure contributing to low discharge temperature.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check the installation conditions and ensure a secure connection of the discharge temperature thermistor (TH4).

  2. 2

    Inspect the holder of the discharge temperature thermistor for any defects or improper seating that could affect temperature sensing.

  3. 3

    Check the coil of the linear expansion valve for disconnection or loose connections.

  4. 4

    Check the connection and contact of the LEV-A and LEV-B connectors on the outdoor controller circuit board.

  5. 5

    Check the linear expansion valve for proper operation, referring to section 10-6 for diagnostic procedures.