E8 (6810)
Indoor/Outdoor Unit Communication Error (Outdoor Receiving)
Mitsubishi Electric · PUZ-HA30/36NHA4 Outdoor Unit
Was bedeutet E8 (6810) ?
The outdoor controller circuit board fails to receive any signal normally for 10 minutes. This can be caused by contact failure in the indoor/outdoor unit connecting wire, defective communication circuits in either the outdoor controller board or the indoor controller board, or noise interference within the indoor/outdoor unit connecting wire.
Häufige Ursachen
- Outdoor unit fails to receive communication signals from indoor unit.
- Damaged or disconnected communication wiring.
- Faulty indoor unit control board.
- Interference on the communication line.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Check for disconnection or looseness of the indoor/outdoor unit connecting wire at both the indoor and outdoor units.
- 2
Turn the power off, then on again. If the abnormality reappears, replace the indoor controller board or outdoor controller circuit board.