Speed Change Gear Arrangement Conflict
Mitsubishi Electric · MELSEC iQ-R Motion Controller
Was bedeutet 1C08H ?
This minor error occurs when both Speed Change Gear 1 ([Pr.434]) and Speed Change Gear 2 ([Pr.490]) are configured with the same arrangement setting. This duplicate arrangement prevents the synchronous control from starting, as the system cannot unambiguously apply speed change processing for the same section of the shaft.
Häufige Ursachen
- The arrangement setting of "[Pr.434] Speed change gear 1" (0 to 3) is identical to the arrangement setting of "[Pr.490] Speed change gear 2" (0 to 3).
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Verify the current setting of "[Pr.434] Speed change gear 1" (valid values: 0, 1, 2, 3).
- 2
Verify the current setting of "[Pr.490] Speed change gear 2" (valid values: 0, 1, 2, 3).
- 3
Modify either "[Pr.434] Speed change gear 1" or "[Pr.490] Speed change gear 2" to ensure their arrangement settings are distinct from each other.