Übersetzen...
TRIAC-NO-OFF-LOW-CURRENT

Triac Output Not Turning Off (Low Load Current)

Mitsubishi Electric · MELSEC iQ-R I/O Module

Was bedeutet TRIAC-NO-OFF-LOW-CURRENT ?

The triac output fails to turn off when the load current is too low (below 25mA). In such conditions, the triac may not operate stably. If an inductive load is connected, the surge current during turn-off can keep the phototriac component in the triac active, preventing complete deactivation.

Häufige Ursachen

  • Load current is below the minimum required operating current for stable triac operation (less than 25mA).
  • Inductive loads causing a turn-off surge that sustains activation of the phototriac within the triac module.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Connect a resistor in parallel across the load terminals to increase the total current flow to approximately 100mA, thereby ensuring stable triac operation and proper turn-off.

  2. 2

    Calculate the resistance value (R) required using the formula: R ≤ (Voltage across the load) ÷ 100mA. For example, for a 100VAC output, a 1kΩ resistor is suitable.

Alle Codes in diesem Handbuch durchsuchen (56)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Mitsubishi Electric MELSEC iQ-R I/O Module