Übersetzen...
INPUT-SNEAK-PATH
Input Sneak Path Current (Multiple Power Supplies)
Mitsubishi Electric · MELSEC iQ-R I/O Module
Was bedeutet INPUT-SNEAK-PATH ?
An input signal does not turn off due to a sneak path current created by the use of two power supplies in the system. This unintended current flow bypasses the intended circuit, keeping the input module falsely activated, especially when voltage E1 is greater than E2.
Häufige Ursachen
- Use of two power supplies in the input circuit where voltage differences (E1 > E2) create an unintended current path (sneak path).
- Incorrect wiring configuration leading to alternative current routes that keep the input signal active.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Consolidate the input circuit to use a single power supply to eliminate the conditions for a sneak path.
- 2
If two power supplies are absolutely necessary, connect a diode in series with the input device to block any reverse current flow and prevent the sneak path.
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026
Verwandte Fehlercodes
Quelle: Mitsubishi Electric MELSEC iQ-R I/O Module