CHATTERING-INPUT

Input Data Incorrect (Chattering)

Mitsubishi Electric · MELSEC iQ-R I/O Module

Was bedeutet CHATTERING-INPUT ?

Incorrect input data is received due to chattering when a device with a high input response speed is connected to a contact output module. The rapid, transient fluctuations from contact bounce are interpreted as multiple, unstable input signals, leading to erroneous data processing.

Häufige Ursachen

  • Connection of a device with a high input response speed to a contact output module.
  • Contact chattering or bounce from the input device generating unstable signals.
  • Inability of the contact output module to adequately filter rapid, fluctuating input signals.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Replace the contact output module with a transistor output module when interfacing with devices that have a high input response speed to mitigate chattering effects.